AT High Strength Acrylic-Tie® Anchoring Adhesive

Tension and Shear Loads for Threaded Rod Anchors in

Lightweight, Medium-Weight and Normal-Weight Hollow CMU

 
Tension Load Shear Load Threaded Rod Concrete Block (CMU)
Anchor Installed in Face Shell with Stainless-Steel Screen Tube (see figure 4)
Tension and Shear Loads for Threaded Rod Anchors in Light-Weight, Medium-Weight and Normal-Weight Hollow CMU
  1. Threaded rods must comply with ASTM A 307 minimum.
  2. Values for 6 and 8-inch wide CMU Grade N, Type II concrete masonry units conforming to UBC Standard 21-4 or ASTM C90. The masonry units, when grouted, must be fully grouted with grout complying with UBC Section 2103.4, or IBC Section 2103.12. Mortar is prepared in accordance with Section 2103.3 of the UBC and UBC Standard 21-15, or IBC Section 2103.8. The minimum specified compressive strength of masonry, f'm, at 28 days is 1,500 psi.
  3. Embedment depth is measured from the outside face of the concrete masonry unit for installations through a face shell.
  4. Allowable loads may not be increased for short-term loading due to wind or seismic forces.
  5. Refer to In-Service Temperature Sensitivity Chart for allowable load adjustment for temperature.
  6. The tabulated allowable loads are based on a safety factor of 5.0 for installations under the IBC and IRC. For installations under the UBC use a safety factor of 4.0 (multiply the tabulated allowable loads by 1.25).
  7. Anchors must be spaced a minimum distance of four times the anchor embedment.
Figure 4: Anchor installed in face shell w/screen tube in hollow cell
Anchor installed in face shell w/screen tube in hollow cell
 
Tension Load Shear Load Threaded Rod Concrete Block (CMU)
Anchor Installed in Face Shell with ATSP (Plastic) Screen Tube

  1. Threaded rods must comply with ASTM A 307 minimum.
  2. The tabulated allowable loads are based on a safety factor of 5.0 for installations under the IBC and IRC. For installations under the UBC use a safety factor of 4.0 (multiply the tabulated allowable loads by 1.25).
  3. Edge distances may be reduced to 4" with a corresponding 37% reduction in tension capacity. Shear capacity is unaffected.
  4. Values for 8-inch wide CMU Grade N, Type II, lightweight, medium-weight and normal weight concrete masonry units conforming to UBC Standard 21-4 or ASTM C90 with min compressive strength of 1,900 psi and 1 1/4" thick face shell.
  5. Mortar is prepared in accordance with UBC Section 2103.3 and UBC Standard 21-15, or IBC Section 2103.8.
  6. Embedment depth is measured from the outside face of the concrete masonry unit.
  7. Refer to In-Service Temperature Sensitivity Chart for allowable load adjustment for temperature.
  8. Allowable loads may not be increased for short-term loading due to wind or seismic forces. Wall design must satisfy applicable design standards and be capable of withstanding applied loads.
 