Anchor Installed in Face Shell with Stainless-Steel Screen Tube (see figure 4)
- Threaded rods must comply with ASTM A 307 minimum.
- Values for 6 and 8-inch wide CMU Grade N, Type II concrete masonry units conforming to UBC Standard 21-4 or ASTM C90. The masonry units, when grouted, must be fully grouted with grout complying with UBC Section 2103.4, or IBC Section 2103.12. Mortar is prepared in accordance with Section 2103.3 of the UBC and UBC Standard 21-15, or IBC Section 2103.8. The minimum specified compressive strength of masonry, f'm, at 28 days is 1,500 psi.
- Embedment depth is measured from the outside face of the concrete masonry
unit for installations through a face shell.
- Allowable loads may not
be increased for short-term loading due to wind or seismic
forces.
- Refer to In-Service Temperature Sensitivity Chart for
allowable load adjustment for temperature.
- The tabulated allowable loads are based on a safety factor of 5.0 for installations under the IBC and IRC. For installations under the UBC use a safety factor of 4.0 (multiply the tabulated allowable loads by 1.25).
- Anchors must be
spaced a minimum distance of four times the anchor embedment.