Tension and Shear Loads in Normal-Weight Concretes
Tension and Shear Loads in Sand-Lightweight Concrete over Metal Deck
Tension and Shear Loads in Normal-Weight Concrete
- The allowable loads listed are based on a safety factor of 4.0.
- The minimum concrete thickness is 1 1/2 times the embedment depth.
- Allowable loads may be linearly interpolated between concrete strengths listed.
- For rod coupler, mechanical and plumbing design codes may prescribe lower allowable loads; verify with local codes.
Tension and Shear Loads in Sand-Lightweight Concrete over Metal Deck
- The allowable loads listed are based on a safety factor of 4.0.
- The minimum concrete thickness is 1 1/2 times the embedment depth.
- Anchors may be installed off-center in the flute, up to 1" from the center of flute.
- Anchor may be installed in either upper or lower flute.
- Deck profile shall be 3" deep, 20-gauge minimum.
- For rod coupler, mechanical and plumbing design codes may prescribe lower allowable loads; verify with local codes.