Tension and Shear Load Values in Face Shell

of Hollow and Grout-Filled CMU

Information on this page has been updated since the printing of the 2008 Anchor Systems Catalog (C-SAS-2008).
To view the specific changes made to this page in detail, see Catalog Errata.
 
Tension Load Shear Load Concrete Block (CMU)
Titen Tension and Shear Load Values in Face Shell of Hollow and Grout-Filled CMU
  1. The tabulated allowable loads are based on a safety factor of 5.0 for installations under the IBC and IRC. For installations under the UBC use a safety factor of 4.0 (multiply the tabulated allowable loads by 1.25).
  2. Spacing may be reduced 50% with a corresponding 50% reduction in allowable tension and shear load capacities.
  3. Edge distances may be reduced 50% with a corresponding 50% reduction in allowable tension and shear load capacities.
  4. Linear interpolation may be used for intermediate spacing and edge distances.
  5. Maximum anchor embedment is 1 1/2" (38.1 mm).